No-load + blocked-rotor tests
Two bench tests — the direct parallel of transformer OC/SC — that pin down every equivalent-circuit parameter.
Step 1 — Two bench tests pin down every equivalent-circuit parameter
Reference notes
Use Next → on the narrator above to step through both bench tests and watch the parameter table fill in.
Two tests, full equivalent circuit — the direct parallel of transformer OC/SC
An induction motor's per-phase equivalent circuit has the same shape as a transformer's. The same two-test trick pins down every parameter:
- No-load (NL) test — apply rated voltage, no shaft load. Measures the shunt branch: core loss, magnetising reactance.
- Blocked-rotor (BR) test — mechanically lock the rotor, apply a reduced voltage to drive rated current. Measures the series branch: stator + referred rotor resistance and leakage reactance.
No-load test — measures the shunt branch
- Setup: rated three-phase voltage applied to the stator; rotor uncoupled from any load. The rotor runs at near-synchronous speed (slip ≈ 0).
- Measure: VNL, INL, PNL.
- What we learn: at very small slip, R2/s is enormous → no current flows in the rotor branch → essentially all the current flows in the shunt magnetising branch. PNL equals (essentially) the core loss plus a small amount of friction & windage.
From the readings (per-phase):
Rc = VNL² / Pcore Xm = VNL² / QNL
(after subtracting stator copper loss INL²·r1 and the friction-windage component from PNL, which is usually obtained from a separate spin-down test).
Blocked-rotor test — measures the series branch
- Setup: mechanically lock the rotor (s = 1, like a stalled motor). Apply a reduced voltage and crank it up until rated current flows.
- Measure: VBR, IBR, PBR.
- Why a reduced voltage? Because at standstill R2/s = R2 is small — full rated voltage would drive 5–7 × rated current. We need only enough V to push rated current through the small series impedance.
- What we learn: at low VBR, the magnetising current is negligible (the shunt branch is "starved"). All the current flows through the series branch. PBR equals (essentially) the rotor + stator copper losses at rated current — i.e. the full-load copper loss.
From the readings:
The stator r1 is usually measured separately by DC-resistance test, and r2′ = Req − r1. The leakage reactance splits roughly equally between stator and rotor (a common approximation in design problems).
Why these two tests work in tandem
The NL test isolates the shunt branch by making the series branch (rotor) carry essentially no current. The BR test isolates the series branch by starving the shunt branch with a low voltage. Each test eliminates the other's effect, and between them they pin down every parameter the equivalent circuit needs. Exactly the same logic as the transformer's OC/SC tests.
What you can compute once you have all the parameters
- Steady-state operating point at any slip: stator current, power factor, efficiency.
- The full torque-slip curve (previous lesson).
- The famous circle diagram — locus of stator current as load varies, on the complex plane. A two-test graphical construction that reads off all operating-point information at once.
- Starting current and starting torque for protection and starter sizing.
Keyboard shortcuts
- → next step · ← previous step
- R replay narration · M mute / unmute · F fullscreen