Equivalent circuit + OC and SC tests
Two simple lab tests that pin down every parameter of the transformer's equivalent circuit.
Step 1 — The full equivalent circuit of a transformer
Reference notes
Use Next → on the narrator above to step through six configurations: from the full equivalent circuit, to the approximate form, to the open-circuit and short-circuit lab tests that pin down every parameter. Sample numbers correspond to a 5 kVA, 240/120 V single-phase transformer.
The transformer's equivalent circuit
Each winding has resistance and leakage reactance. The iron core, in parallel, has a magnetising reactance Xm (which carries the no-load magnetising current) and a core-loss resistance Rc (which represents hysteresis + eddy-current losses). The full per-phase equivalent circuit, with the secondary already referred to the primary side, looks like:
where a = N₁ / N₂ is the turns ratio. Multiplying the secondary impedances by a² is the standard "impedance referral" — it lets us analyse the whole transformer on a single side.
The approximate equivalent circuit
Because the magnetising current is small (a few per cent of rated current), the voltage drop across r₁ and jx₁ due to just the magnetising current is also small. We push the shunt branch all the way to the input terminals and combine the remaining series elements:
So the approximate model has just three elements: a shunt branch Rc ‖ jXm at the input terminals, and a series Req + jXeq in front of the load. This is the form we use for almost all hand calculations.
The open-circuit (OC) test — measures the shunt branch
- Setup: apply rated voltage on the LV side, leave the HV side open. Measure Voc, Ioc, and Poc.
- Why LV side? A low test voltage is easier and safer to apply. With the HV open there's no current in the series branch — only the magnetising and core-loss currents flow through the shunt branch.
- What it gives us: Poc equals the core loss at rated voltage (essentially constant regardless of load). From Voc, Ioc, Poc we extract the shunt-branch parameters Rc and Xm.
The short-circuit (SC) test — measures the series branch
- Setup: short-circuit the LV side (or in some conventions HV — either works), and apply a reduced voltage on the other side until rated current circulates. Measure Vsc, Isc, Psc.
- Why a reduced voltage? Because the impedance is small, only a small fraction of rated voltage is needed to drive rated current. At this low voltage the magnetising current is negligible — the shunt branch is essentially "off" — so what we measure is purely the series impedance.
- What it gives us: Psc equals the full-load copper loss (because rated current is flowing). From Vsc, Isc, Psc we extract the series-branch parameters Req and Xeq.
Keyboard shortcuts
- → next step · ← previous step
- R replay narration · M mute / unmute