Dashboard Deep Learning Power Systems Analysis Fault analysis Unbalanced fault analysis — sequence networks (LG / LL / LLG / 3-φ)

Unbalanced fault analysis — sequence networks (LG / LL / LLG / 3-φ)

Symmetrical-component analysis via Fortescue decomposition: connect positive / negative / zero sequence networks per fault type — LG=series, LL=pos∥neg, LLG=pos series with (neg∥zero), 3-φ=pos only. Z1, Z2, Z0 per generator / transformer / line. ETAP / SKM / EasyPower / PowerWorld automate via sequence Y-bus / Z-bus.

Senior ~13 min

Step 1 — Symmetric vs unbalanced faults: sequence-network analysis

0.55×
type I_fault seq cnx

Reference notes

Most transmission-system faults are unbalanced. Balanced 3-phase faults occur in only 5-10% of cases; single line-to-ground (LG) faults dominate at 70-80%. Unbalanced fault analysis uses symmetrical components — the Fortescue decomposition into positive, negative, and zero sequence networks — with sequence networks connected differently per fault type.

Fault-type frequency distribution

Fault typeFrequencyI_fault formulaSeq-network connection
3-φ balanced5-10%I_3φ = V_pre / Z1Positive sequence only
LG (single line-to-ground)70-80%I_LG = 3·V_pre / (Z1+Z2+Z0)Pos + Neg + Zero in SERIES
LL (line-to-line)10-15%I_LL = (√3/2) · I_3φ ≈ 0.866 · I_3φPos ∥ Neg (no zero)
LLG (double line-to-ground)5-10%depends on Z0Pos series with (Neg ∥ Zero)

Symmetrical components — Fortescue (1918)

LG fault — single line-to-ground (70-80% of faults)

LL fault — line-to-line (10-15%)

LLG fault — double line-to-ground (5-10%)

3-φ balanced fault (5-10%)

Sequence impedances by component

LG vs 3-φ fault current — depends on Z0/Z1 ratio

I_LG / I_3φ = 3 / (2 + Z0/Z1) (with Z1 = Z2)

Modern fault-study workflow

Take-away. Most faults are unbalanced — LG dominates at 70-80%, LL 10-15%, LLG 5-10%, 3-φ only 5-10%. Symmetrical-component (Fortescue) analysis decomposes unbalanced phasors into positive/negative/zero sequence networks. Connection rule per fault type: LG=series, LL=positive∥negative (no zero), LLG=positive series with (negative∥zero), 3-φ=positive only. Each element (generator, transformer, line) has Z1, Z2, Z0. Wye-delta transformer isolates zero-sequence between primary and secondary. Modern tools (ETAP, SKM, EasyPower, PowerWorld) automate the calculation by building sequence Y-bus / Z-bus matrices and applying fault-type rules at every bus.