Overcurrent protection & TCC coordination
ANSI 50/51, IEEE TCC curves, pickup + time-dial settings, and coordination of cascaded protective devices with CTI.
Step 1 — ANSI 50 (instantaneous) and 51 (time-overcurrent) elements
Reference notes
Use Next → on the narrator above to step through overcurrent protection and time-current-characteristic coordination — the most common protection topic on the PE Power exam.
ANSI device numbers
- 50 — instantaneous overcurrent. Trips with no intentional delay when current exceeds a high threshold.
- 51 — time-overcurrent. Trips after a delay that depends on the current level, with an inverse-time characteristic.
- 50N / 51N — residual ground-fault elements (driven by the sum of phase CTs through a neutral path).
- 67 / 67N — directional overcurrent (adds a polarizing voltage or sequence input to distinguish forward from reverse fault flow). Required on parallel-source or ring topologies.
TCC curve mathematics
The IEEE C37.112 standard inverse curve family is:
where:
- t = trip time, seconds
- TD = time-dial multiplier (selected by the engineer; typically 0.5 to 10)
- M = I / Ipickup (current as a multiple of pickup)
- A, B, p = curve-shape constants per the table below
| Curve | A | B | p | Used with |
|---|---|---|---|---|
| Moderately inverse (MI) | 0.0515 | 0.114 | 0.02 | General feeders |
| Inverse (NI) | 5.95 | 0.180 | 2 | Default for line/feeder protection |
| Very inverse (VI) | 3.88 | 0.0963 | 2 | Tight coordination with downstream |
| Extremely inverse (EI) | 5.67 | 0.0352 | 2 | Pairing with fuses (matches I²t melt curve) |
Setting the pickup
Pickup is the current below which the time-overcurrent element will never trip. Standard practice:
- Feeder breaker: pickup ≈ 1.25 × maximum continuous load current (rides through cold-load inrush, harmonics, motor starting).
- Motor protection: pickup ≈ 1.5 × motor FLA (rides through normal start inrush of ~6× FLA for a few seconds).
- Transformer primary: pickup ≈ 1.0 × FFLA (full-load amps), with NEC 450.3 maximum at 250–600 % depending on configuration.
- Ground fault (51N): pickup ≈ 10–20 % of phase pickup, low enough to detect arcing ground faults that don't trip the phase elements.
Setting the time-dial
Once pickups are chosen, set the time-dial (TD) so the upstream device's curve sits the required CTI above the downstream device's curve at the maximum fault current. Procedure:
- Pick the most-downstream device's curve shape and pickup. Set its TD to give minimum acceptable trip time at the maximum fault.
- For the next device upstream: compute the downstream device's trip time at the max-fault current it would see. Add the CTI. Solve the TCC equation for the TD that gives this total trip time at the same current.
- Repeat all the way to the utility interface.
Coordination time interval (CTI)
The minimum vertical gap between adjacent TCC curves at the maximum fault current. Typical values:
- 0.30 s with modern microprocessor relays and MV vacuum breakers.
- 0.40 s with older electromechanical relays.
- 0.20 s with very fast LV breakers (e.g., insulated-case or air circuit breakers).
The CTI budget breaks down roughly as: breaker opening time (5 cycles ≈ 0.083 s for MV vacuum), relay overtravel (~0.05 s for electromechanical, ~0 for digital), and a safety margin (~0.15 s).
Coordination example
Three devices in series: MCC feeder → plant main → utility incomer. At the maximum 3-φ fault current at the MCC bus:
- MCC feeder curve should trip in ~0.10 s.
- Plant main curve should be at ~0.40 s (0.30 s above).
- Utility curve should be at ~0.70 s (another 0.30 s above).
Each layer of protection provides backup for the layer below — if the MCC breaker fails, the plant main clears the fault 0.30 s later; if both fail, the utility breaker clears 0.30 s after that. This is "fully selective" coordination.
Keyboard shortcuts
- → next step · ← previous step
- R replay narration · M mute / unmute · F fullscreen
- Click anywhere on the TCC plot to move the fault-current cursor and see which device trips first.