Symmetrical components — Fortescue decomposition
Any three unbalanced phasors split uniquely into a balanced positive-sequence + a balanced negative-sequence + a zero-sequence set. The algebra behind all unbalanced fault analysis.
Step 1 — Unbalanced 3-phase set: per-phase analysis breaks down
Reference notes
Use Next → on the narrator above to step through Fortescue's decomposition: the unbalanced raw set, the three balanced sequence sets (positive, negative, zero), the decomposition formulae, and where the technique shows up in real power-system analysis.
Why we need this
Per-phase analysis assumes balanced three-phase: three equal magnitudes, exactly 120° apart. Most steady-state load-flow studies fit that assumption. But unbalanced conditions — single line-to-ground faults, open conductors, unbalanced loads, non-linear-load harmonics — destroy the symmetry, and a per-phase model can no longer give the right answer. Symmetrical components rescue us: any three phasors can be uniquely decomposed into three balanced sets that can be analyzed per-phase, then re-superposed.
The three sequence sets
Positive sequence (+)
Three equal-magnitude phasors, 120° apart, rotating in the same sense as the original system (A → B → C). With a = 1∠120° as the rotation operator:
This is the "normal" component — it carries real power, produces torque in motors, and is what you'd see in a perfectly balanced system.
Negative sequence (−)
Three equal-magnitude phasors, 120° apart, but rotating in the opposite sense (A → C → B). The a and a² roles swap relative to positive sequence:
Negative sequence shows up only under unbalance. In a motor it produces a braking torque, induces rotor losses, and is what relay 46 (negative-sequence overcurrent) trips on.
Zero sequence (0)
Three equal-magnitude phasors, all in phase — no rotation at all:
Their sum is 3 V₀, not zero. That means zero-sequence currents need a return path (neutral wire or earth) to flow. With no neutral, zero-sequence current is forced to zero by KCL. Triplen harmonics (3rd, 9th, 15th, …) are zero-sequence — they're in phase across all three phases, so a delta winding captures them as circulating currents and a tertiary delta protects the rest of the system from harmonic distortion.
The Fortescue decomposition formulae
Given any three phase phasors Va, Vb, Vc:
Notice the elegant symmetry: in V₊ we multiply V_b by a and V_c by a²; in V₋ we swap them. And reconstruction is just addition:
Where this matters in practice
Single line-to-ground fault
SLG faults are the most common power-system fault (about 70–80% of all faults). For a fault on phase a with the others healthy, the boundary conditions are Ib = Ic = 0 and Va = Zf · Ia. Substituting into the Fortescue matrix yields:
So in the sequence-network model, the three networks (Z₊, Z₋, Z₀) are connected in series. The fault current is:
where Zf is the fault impedance (often taken as zero for bolted faults). Other fault types reduce to other interconnections of the same three sequence networks.
Transformer zero-sequence behaviour
- Yy0 with both neutrals grounded: zero-sequence sees the same path as positive.
- Yy0 with isolated neutrals: zero-sequence is blocked on both sides — open circuit in the Z₀ network.
- Yd with grounded Y: Z₀ provides a path on the Y side that ends in the delta (which presents short to neutral from the rest of the system's view). On the delta side: open.
- Dd: zero-sequence cannot enter or leave on either side.
The structural rule: a delta winding always blocks zero-sequence from crossing it; a grounded wye provides a path.
Motor protection
Continuously running an induction motor on unbalanced supply produces both negative-sequence current (which heats the rotor disproportionately) and a torque component opposing rotation. The standard rule of thumb is that a 5% voltage unbalance causes ~30% increase in motor losses — which is why ANSI relay 46 (negative-sequence overcurrent) is a core induction-motor protection element.
Keyboard shortcuts
- → next step · ← previous step
- R replay narration · M mute / unmute · F fullscreen