Voltage regulation across power factors
Why terminal voltage drops on lagging loads — and actually rises on leading loads.
Step 1 — What voltage regulation means: the gap between V_NL and V_FL
Reference notes
Use Next → on the narrator above to walk through six steps that build the secondary-side phasor construction, derive the approximate regulation formula, and sweep the load power factor from heavy lagging through unity to leading.
What "voltage regulation" actually means
For a transformer, the no-load secondary voltage VNL is what V₂ would be if you suddenly opened the load — basically V₁/a, the source's view of the secondary. When you apply rated load, the actual terminal voltage V₂ is lower by an amount that depends on the load current and the equivalent series impedance Req + jXeq. Voltage regulation is the percent drop:
Regulation scales with load — at half load the drops are half, so the regulation is roughly half. At constant load, it depends on the load power factor.
The phasor construction
Place V₂ along the reference and let the load current I₂ sit at angle θ behind V₂ (lagging) or ahead (leading). The two equivalent series-impedance drops are:
- I₂·Req — in phase with I₂ (resistive drop)
- I₂·Xeq — 90° leading I₂ (inductive drop)
Adding them tip-to-tail to V₂ gives VNL:
The magnitude of VNL minus V₂ is the regulation — a small number, but on a power system carrying tens of MW, very much worth getting right.
The approximate regulation formula
For small drops (a few per cent of V₂), the bend in the phasor triangle is tiny and we can just project the drops onto the V₂ direction:
where εr = I₂·Req / V₂ and εx = I₂·Xeq / V₂ are the per-unit resistive and reactive drops at full load. The sign of the second term depends on the power factor:
- Lagging PF uses +εx·sin θ — both terms are positive, regulation is at its largest.
- Unity PF kills the sin θ term — regulation reduces to about εr alone (a small positive number).
- Leading PF uses −εx·sin θ — the two terms can subtract enough to make the whole thing negative, meaning the no-load voltage is smaller than the full-load voltage. In other words, the secondary terminal voltage rises when you connect the load.
Maximum regulation
Differentiating the approximate formula with respect to θ shows that regulation is maximum when the load PF angle equals the equivalent-impedance angle:
and the maximum value equals the per-unit magnitude of the equivalent impedance, εz = √(εr² + εx²).
Why this matters in practice
- Distribution transformers feeding industrial loads (motors, fluorescent lights) see lagging PF → larger regulation, so terminal voltage sags. PF-correction capacitor banks pull the load PF closer to unity to limit the sag.
- Long, lightly-loaded transmission lines feeding into a transformer can present a leading load (line-charging capacitance dominates) → negative regulation, with terminal voltage rising at full load. Utilities have to actively manage this.
- The same equivalent-circuit parameters (Req, Xeq) we extracted from the SC test in the previous lesson are exactly what we need here. The two lessons fit together: SC test measures the parameters; regulation uses them to predict behaviour.
Keyboard shortcuts
- → next step · ← previous step
- R replay narration · M mute / unmute