Dashboard PE Power Exam Prep Electric Power Devices Transformers Voltage regulation across power factors

Voltage regulation across power factors

Why terminal voltage drops on lagging loads — and actually rises on leading loads.

Freshman ~8 min

Step 1 — What voltage regulation means: the gap between V_NL and V_FL

0.55×
cos θ 1.00 |VNL| 1.00 Reg 0.0%

Reference notes

Use Next → on the narrator above to walk through six steps that build the secondary-side phasor construction, derive the approximate regulation formula, and sweep the load power factor from heavy lagging through unity to leading.

What "voltage regulation" actually means

For a transformer, the no-load secondary voltage VNL is what V₂ would be if you suddenly opened the load — basically V₁/a, the source's view of the secondary. When you apply rated load, the actual terminal voltage V₂ is lower by an amount that depends on the load current and the equivalent series impedance Req + jXeq. Voltage regulation is the percent drop:

Regulation = (VNL − VFL) / VNL × 100 %

Regulation scales with load — at half load the drops are half, so the regulation is roughly half. At constant load, it depends on the load power factor.

The phasor construction

Place V₂ along the reference and let the load current I₂ sit at angle θ behind V₂ (lagging) or ahead (leading). The two equivalent series-impedance drops are:

Adding them tip-to-tail to V₂ gives VNL:

VNL = V₂ + I₂·(Req + jXeq)

The magnitude of VNL minus V₂ is the regulation — a small number, but on a power system carrying tens of MW, very much worth getting right.

The approximate regulation formula

For small drops (a few per cent of V₂), the bend in the phasor triangle is tiny and we can just project the drops onto the V₂ direction:

Regulation ≈ εr·cos θ ± εx·sin θ

where εr = I₂·Req / V₂ and εx = I₂·Xeq / V₂ are the per-unit resistive and reactive drops at full load. The sign of the second term depends on the power factor:

Maximum regulation

Differentiating the approximate formula with respect to θ shows that regulation is maximum when the load PF angle equals the equivalent-impedance angle:

θmax = arctan(Xeq / Req) ≡ φz

and the maximum value equals the per-unit magnitude of the equivalent impedance, εz = √(εr² + εx²).

Why this matters in practice

Take-away. Voltage regulation is the lens through which you see how a transformer's series impedance interacts with the load's power factor. Lagging loads bleed voltage; unity loads cause a small drop; leading loads can actually raise it. The phasor construction and the approximate formula are two views of the same thing — pick whichever feels more intuitive on the day.

Keyboard shortcuts