Three-phase fault analysis — symmetrical and unbalanced
Thevenin reduction, 3-φ symmetrical fault, sequence networks for SLG / LL / DLG, fault impedance, breaker sizing, motor contribution.
Step 1 — Thevenin reduction: system → V_th + Z_th at the fault bus
Reference notes
Use Next → on the narrator above to step through fault analysis: Thevenin reduction, symmetrical 3-φ faults, component sequence impedances, single line-to-ground faults (the most common type), other unbalanced faults, and practical fault-impedance + breaker-rating + motor-contribution considerations.
The Thevenin reduction
Every fault calculation starts by reducing the network behind the fault to a Thevenin equivalent at the fault bus: a pre-fault voltage source Vth in series with a Thevenin impedance Zth. Vth is typically taken as 1.0 pu (the pre-fault nominal voltage). Zth is computed by combining generator subtransient reactances, transformer leakage impedances, and line impedances in the appropriate parallel-series fashion, all expressed in per-unit on a common base.
Symmetrical three-phase fault
All three phases short to each other through a low impedance. By symmetry only the positive-sequence network is active:
Worked example on a 100 MVA, 13.8 kV system with Z_+ = 0.10 pu, bolted fault:
- I_pu = 1.0 / 0.10 = 10 pu
- I_base = 100·10⁶ / (√3 · 13 800) ≈ 4184 A → I_fault ≈ 42 kA
- S_SC = 100 / 0.10 = 1000 MVA
Component sequence impedances
Each piece of equipment has three impedances:
| Component | Z+ | Z− | Z0 |
|---|---|---|---|
| Static (transformer, line) | X_leakage | = Z_+ | depends on grounding |
| Synchronous turbo generator | X_d″ ≈ 0.15–0.25 pu | ≈ X_d″ to 0.1·X_d″ | very low (0.02–0.05 pu) |
| Synchronous hydro generator | X_d″ ≈ 0.20–0.40 pu | ~0.2·X_d″ | low |
| Induction motor | X_lr (locked-rotor) | ≈ X_lr | no contribution |
Zero-sequence behaviour is dominated by the grounding scheme:
- Solidly grounded Y_n: low Z0, often comparable to Z+. SLG can equal or exceed 3-φ fault.
- Resistance-grounded: Z0 dominated by the grounding resistor, limiting SLG current to tens or hundreds of amps.
- Isolated / ungrounded: Z0 = ∞; SLG produces only capacitive charging current (a few amps), but the unfaulted phases see VLL instead of VLN, stressing insulation.
- Delta winding: presents open circuit to zero-sequence trying to cross the transformer.
Single line-to-ground (SLG) fault
The most common fault type (70–80%). Boundary conditions on a phase-a SLG fault: I_b = I_c = 0 and V_a = Z_f · I_a. Substituting into the Fortescue transform:
The three sequence networks connect in series. The 3·Zf appears because all three sequence currents flow through the same physical fault impedance.
Other unbalanced faults
- Line-to-line (LL): two phases bolt to each other, no ground. Z0 is out. Sequence networks: Z+ and Z− in series. I+ = Vth/(Z+ + Z− + Zf); Ifault,b = √3 · I+.
- Double line-to-ground (DLG): two phases bolt to each other AND to ground. All three sequence networks active. Z+ in series with the parallel combination Z− ∥ (Z0 + 3·Zf).
Practical considerations
Fault impedance Zf
Bolted metallic fault: Zf ≈ 0. Arcing fault: typically a few ohms to tens of ohms (the arc-voltage drop divided by arc current). Tree contact, contact resistance, soil resistance: highly variable. High-impedance ground faults often sit below overcurrent settings and are detected only by sensitive ground-fault relays.
Breaker interrupting rating
The breaker must clear the maximum first-cycle fault current at its location. Standard ratings: 22, 42, 65, 100, 200 kA RMS symmetrical. The asymmetrical (peak with DC offset) rating is roughly 2.6× the symmetrical RMS rating immediately after fault initiation.
Motor contribution
Every running motor over ~50 hp briefly contributes to fault current for the first ~6 cycles via stored kinetic energy and air-gap flux. The contribution magnitude is approximately 4–6× the motor's rated current (governed by X_d″ or locked-rotor reactance), decaying as the motor decelerates. IEEE Std 141 (Red Book) and IEC 60909 give standardised procedures for including motor contribution in industrial fault studies.
Keyboard shortcuts
- → next step · ← previous step
- R replay narration · M mute / unmute · F fullscreen
- On steps 3–6, click the fault-type buttons (3-φ / SLG / LL / DLG) on the canvas to switch the sequence-network interconnection.