Dashboard PE Power Exam Prep Protection Overcurrent & coordination Differential (87) and distance (21) protection

Differential (87) and distance (21) protection

KCL-based unit protection plus impedance-plane mho zones for transmission lines — the two fastest, most selective protections on the grid.

Sophomore ~12 min

Step 1 — Differential (87) and distance (21): two complementary protections

0.55×
I_in/I_out 1.00 Z_fault decision

Reference notes

Use Next → on the narrator above to step through the two workhorse "fast-acting" protections: differential (ANSI 87) for unit equipment, and distance (ANSI 21) for transmission lines.

Differential protection — ANSI 87

87 applies Kirchhoff's current law (Σ-of-currents = 0) to the protected zone. CTs at every boundary measure the current flowing into and out of the zone. For external loads or external faults, ΣIin = ΣIout and the difference is ideally zero:

Iop = |Iin − Iout|

For an internal fault, the fault current bypasses the output CT — I_op becomes large and the relay trips.

Percentage-restraint characteristic

Real CTs are not perfect — at high through-currents they saturate and produce ratio errors of several percent. A fixed pickup would nuisance-trip on external faults. The fix is the percentage-restraint (bias) characteristic:

Trip if Iop > max(Ipickup,min, slope · IR)
where IR = (Iin + Iout) / 2

Slope is typically 20–40 %. Modern relays add a second slope above an inflection point (~3× rated) to ride through severe CT saturation during external faults.

Transformer differential: the 2nd-harmonic trick

Energizing a transformer produces magnetizing inrush — 6–10× rated, all on the primary side with no secondary current. To a plain differential relay this looks identical to an internal fault. The fix exploits the harmonic content: inrush is rich in 2nd harmonic; fault current is not. Transformer differential relays block tripping when 2nd-harmonic content exceeds ~15 % of the fundamental.

Where 87 is used

Distance protection — ANSI 21

21 measures the impedance from the relay terminal to the fault:

Zrelay = Vlocal / Ilocal

For a fault at the far end of the line, Z_relay equals the full line impedance. For a closer fault, Z_relay is smaller. The relay trips when the measured impedance falls within its operating characteristic on the R-X impedance plane.

Mho characteristic

The classic mho is a circle on the R-X plane passing through the origin, with diameter Z_reach along the protected line's angle (typically 75–85° for HV transmission lines). The geometry naturally:

Modern numerical relays often use a quadrilateral (quad) characteristic with adjustable R and X reach boundaries for finer control, especially on lines with significant arc-fault resistance.

Three zones

Pilot schemes — eliminating the 20 % Z1 gap

For lines where instantaneous clearing of the full 100 % is required (HV / EHV), pilot schemes use a communication channel between line ends:

87 vs 21 — when to use which

Property87 differential21 distance
Zone definitionBy CT locations (precise)By reach in impedance (probabilistic)
SelectivityAbsolute — never overreachesDepends on accurate impedance
Speed1 cycle1 cycle (Z1)
Typical useTransformers, generators, buses, motors, short cablesTransmission lines
CoordinationNo time coordination needed — selectivity by zoneZone-2/3 delays coordinate with neighbours
Take-away. 87 applies KCL inside a CT-bounded zone — fast, selective, and used for transformers / generators / buses / motors. 21 measures Z_relay = V/I and trips when the impedance lies inside the mho (or quad) characteristic; three zones with reach 80 / 120 / 250 % and delays 0 / 300 ms / 1 s cover the line and back up the next station. Pilot schemes (POTT / DCB / 87L) eliminate the Z1 gap when full-line instantaneous tripping is required.

Keyboard shortcuts