Dashboard PE Power Exam Prep Protection Overcurrent & coordination NEC Article 430 — motor branch circuit & feeder sizing

NEC Article 430 — motor branch circuit & feeder sizing

Use TABLE FLC (NEC 430.247-430.250) for conductors + branch OCPD; NAMEPLATE FLA only for overload (430.32). Conductors: 125% × FLC (430.22). Branch OCPD: 250% inv-CB / 300% NTD fuse / 175% DE fuse — × FLC (430.52). Overload: 115-125% × FLA. Disconnect ≥115% FLC within sight (430.102). Feeder: 125% LARGEST + 100% OTHERS (430.24). VFDs: Article 430 Part X.

Senior ~14 min

Step 1 — NEC Article 430: motor circuit sizing — FLC from tables, not nameplate

0.55×
FLC conductor branch OCPD
⚠ Verification pending. This lesson references specific NEC Article 430 sections, table values, and percentage multipliers. The author has not had direct access to NCEES-approved NEC reference materials to verify every number against the current code edition. Do not rely on these values for design or exam preparation without cross-checking the NFPA 70 (current edition) directly. The lesson will be updated once authoritative code documents are available.

Reference notes

NEC Article 430 — Motors, Motor Circuits, and Controllers — is the governing code section in the National Electrical Code (NFPA 70) for sizing every component of a motor branch circuit and feeder. The most frequently mis-applied rule: use the TABLE FLC (from NEC Tables 430.247-430.250) for conductors and short-circuit OCPD; use the NAMEPLATE FLA only for overload-relay sizing.

FLC vs FLA — the critical distinction

TermSourceUsed for
Table FLC (full-load current)NEC 430.247 (DC), 430.248 (1-ph), 430.249 (2-ph), 430.250 (3-ph)Conductors (430.22, 430.24), branch OCPD (430.52), disconnect (430.102)
Nameplate FLA (full-load amps)Motor nameplateOverload relay setting ONLY (430.32)

Reasoning: nameplate FLA varies with manufacturer and motor design; table FLC provides a conservative standardized value ensuring the branch circuit handles ANY motor of that horsepower rating. Overload protection, conversely, matches the actual motor's thermal characteristics, so it uses nameplate FLA.

Motor branch-circuit components (in sequence)

  1. Feeder bus
  2. Motor branch-circuit short-circuit / ground-fault OCPD (430.52) — fuse or circuit breaker
  3. Branch-circuit conductors (430.22, sized 125% × FLC)
  4. Motor disconnect (430.102, within sight or lockable)
  5. Motor controller (430.83, the contactor/starter)
  6. Motor overload protection (430.32, thermal or electronic relay)
  7. Motor

NEC 430.22 — Conductor sizing for a single continuous motor

Ampacity ≥ 125% × table FLC

NEC 430.24 — Conductors for two or more motors (feeder)

Feeder ampacity = 125% × LARGEST motor FLC + 100% × all other motor FLCs

NEC 430.52 — Branch-circuit short-circuit / ground-fault protection (OCPD)

Sized as a MULTIPLE of table FLC. Per NEC Table 430.52:

Device typeMultiplier (× FLC)Allowed maximum (per exception)
Non-time-delay (NTD) fuse300%400%
Dual-element / time-delay fuse175%225%
Inverse-time (thermal-magnetic) breaker250%400%
Instantaneous-trip (magnetic-only) MCP800%1300%

NEC 430.32 — Motor overload protection

Protects the MOTOR ITSELF from sustained overload — different from 430.52 which protects the BRANCH CIRCUIT. Uses NAMEPLATE FLA, NOT table FLC.

Motor service factor / temp riseMaximum trip setting
Service factor ≥ 1.15125% × nameplate FLA
Temperature rise marked ≤ 40°C125% × nameplate FLA
Service factor < 1.15115% × nameplate FLA
Sealed-hermetic / submersiblePer nameplate

NEC 430.102 — Motor disconnect

NEC 430.83 — Motor controller

NEC 430.62 — Feeder OCPD for multi-motor circuits

Feeder OCPD = LARGEST motor branch OCPD setting + sum of FLCs of all other motors

NEC 430 Part X — VFD (adjustable-speed drive) special rules (430.120-430.130)

Common compliance errors

PE exam tips

Take-away. NEC Article 430: use TABLE FLC (430.247-430.250) for conductors + branch OCPD; use NAMEPLATE FLA for overload relay only. 430.22 conductors: 125% × FLC. 430.24 feeder: 125% LARGEST + 100% OTHERS. 430.52 branch OCPD: 250% inverse-time CB / 300% NTD fuse / 175% DE fuse / 800% magnetic-only — × FLC. 430.32 overload: 125% (SF≥1.15) or 115% (SF<1.15) of NAMEPLATE FLA. 430.102 disconnect: ≥115% FLC, within sight or lockable. 430 Part X covers VFDs separately. Two distinct protective devices: branch OCPD protects the branch circuit from short circuits; overload protects the motor from sustained overload. Memorize the four percentages — they cover most PE exam motor questions.