Dashboard PE Power Exam Prep Protection Overcurrent & coordination Transformer protection — 87T / 87REF / 63

Transformer protection — 87T / 87REF / 63

ANSI 87T differential primary, 87REF restricted earth fault, percentage-restraint bias + 2nd/5th harmonic blocking, sudden-pressure (63), Buchholz, thermal (26/49). One modern numerical relay (SEL-787 / GE T60 / RET670 / 7UT85).

Senior ~12 min

Step 1 — Transformer protection: ANSI 87T primary + backups

0.55×
ANSI state slope

Reference notes

Power transformers are protected by a layered set of ANSI functions implemented in a modern microprocessor relay (SEL-787, GE T60, ABB RET670, Siemens 7UT85). Use Next → to walk through 87T differential (primary), 87REF restricted earth fault, percentage-restraint biasing, inrush blocking, and the mechanical / thermal protections that complete the package.

ANSI function set

ANSIFunction
87TTransformer differential — primary internal-fault detection
87REFRestricted Earth Fault — wye-winding ground-fault protection
50 / 51Phase overcurrent — backup + downstream coordination
50G / 51GGround overcurrent
63Sudden Pressure relay — rapid oil-pressure rise from arcing
BuchholzGas-collection relay (oil-immersed conservator-tank transformers)
26Hot-spot thermal (RTD)
49Thermal overload (IEEE C57 thermal model)
71Oil-level alarm
Tank GFTank ground-fault (insulation failure to ground)
23Cooling-fan / pump control

87T transformer differential — the cornerstone

Percentage restraint (bias)

External (through) faults create apparent differential from CT errors — without restraint, the relay would falsely trip on big external faults.

Trip if I_diff > slope · I_restraint + pickup

Where I_restraint = (I_pri + I_sec) / 2 or max(I_pri, I_sec). Typical: slope 25 % at low currents, slope 50 %+ at high currents (dual-slope) to ride through CT saturation.

Harmonic blocking

87REF restricted earth fault

87T is desensitized to ground faults near the wye neutral (small fault current limited by neutral grounding impedance, plus relay slope characteristic). 87REF fills this gap:

Sudden pressure (63) and Buchholz

Thermal protections

Redundancy for large units

Large transformers (typically > 100 MVA) use TWO complete protection relays from different manufacturers, each with its own CT sets and trip path. Diverse design protects against manufacturing defects, design bugs, and setting errors. Trip outputs combined via OR. NERC PRC standards require this on bulk-electric-system transformers.

Modern numerical relay implementation

Take-away. Transformer protection layers 87T differential (primary) + 87REF (wye-winding ground) + 50/51 (backup overcurrent) + 63 sudden pressure + Buchholz + 26/49 thermal. 87T uses percentage restraint (slope 25-50 %) and 2nd/5th harmonic blocking to avoid false trips on through-faults / inrush / over-excitation. All implemented in one modern microprocessor relay (SEL-787 / GE T60 / RET670 / 7UT85). Large transformers use two redundant relays from different vendors.